Electrical power

Real power (kW), apparent power (kVA) and reactive power (kVAr) from the switchboard readings, the current a load will draw, and how loaded a generator is.

Supply
Find
V
A
kW

Fill in the fields to see the result.

How it works

Three-phase: apparent power S = √3 × V × I (kVA), real power P = S × cos φ (kW), reactive power Q = √(S² − P²) (kVAr). Single phase leaves out the √3. 440 V, 1,000 A at cos φ 0.8 is 762 kVA, 610 kW.

Generators are rated in kVA (current) and kW (engine). Load sharing and the power factor decide how many generators to run; large motors starting draw several times their running current.